Factory UPS 30KVA UPS for uninterruptible power supply three-phase for medical industry
Description
Brand: Banatton
Place of origin: China
Type: online UPS
Model Number: BNT9300-M 20~300KVA
Phase: Three Phase
Waveform: Pure sine wave
Transfer time: 0ms
Power factor: 0.9
Capacity: 20KVA-300KVA
Protection: short-circuit, over voltages, reverse connection protection
OEM/ODM: Yes
Supply Ability: 5000 Piece/Pieces per Month
Packaging: Carton or wooden box package or as you requested
Features
In today's digital age, businesses rely heavily on technology to operate efficiently. As reliance on electronic devices and systems increases, ensuring uninterrupted power supply becomes critical. This is where uninterruptible power supplies (UPS) come into play, specifically 30KVA UPS for three-phase systems operating on 220V voltage.
The 30KVA UPS is designed to provide backup power to critical equipment during power outages or voltage fluctuations. It protects sensitive electronic equipment from potential damage and helps prevent data loss, ensuring business continuity and productivity.
The distribution of power in a three-phase system is more efficient and balanced compared to a single-phase system. Therefore, it is crucial to have a UPS that can meet the specific requirements of such a system. The 30KVA UPS has a three-phase output capable of catering to the power needs of larger installations, making it ideal for industrial and commercial applications.
The 220V output of the 30KVA UPS is ideal for powering a variety of equipment, including servers, data centers, industrial machinery and critical infrastructure. It provides stable and reliable power, protecting sensitive equipment from potential damage caused by power outages.
One of the key benefits of a 30KVA UPS is its ability to seamlessly transition to battery power in the event of a power failure, ensuring uninterrupted operation of critical systems. This seamless switch helps maintain productivity and prevent costly downtime, ultimately saving the business from potential losses.
Additionally, the 30KVA UPS’s advanced features such as remote monitoring and management capabilities enable proactive maintenance and real-time monitoring of power conditions. This proactive approach helps identify and resolve potential issues before they escalate, improving the overall reliability of the power supply.
In summary, investing in a 30KVA UPS to provide uninterruptible power to three-phase systems is a strategic decision for businesses looking to protect critical equipment and maintain operational continuity. With its powerful features and reliable performance, 30KVA UPS is a valuable asset in preventing power-related outages and ensuring seamless operation of essential systems.
Little Hint
1. In the warranty period the machine has a problem, please contact the sales staff, we will be responsible for customer service.
2. Exceed the warranty period, improper operation and man-made damage, we will still give help and support, we will provide spare parts at a cost price.
3. According to the customer's needs, we can provide unconventional, but the cost may be slightly higher than the traditional machine.
Applications
Data processing center, The host system, Computer servers, Medical, Traffic, Electricity, IT, Industrial and other industries.
Factory Production Line
Packaging
MODEL | BNT990-M | BNT9150/180-M | BNT9300-M | |
Rated Capacity | Cabinet Capacity | 20-90kVA / 20-90kW | 25-150kVA / 25-150kW 30-180kVA / 30-180kW | 30-300kVA / 30-300kW |
One Ppwer Module Capacity | 20kVA /20kW, 25kVA /25kW,30kVA /30kW | |||
MAX. Power Module NO. | 3 | 5/6 | 10 | |
INPUT | ||||
Main Input | Nominal Voltage(Vac) | 380/400/415 | ||
Voltage Range(Vac) | 138~485Vac;305~485Vac load,138~305Vac load | |||
Phase | 3-phase in / 3-phase out | |||
Nominal Frequency(Hz) | 40-70 | |||
Power Factor | ≥0.99 | |||
Harmonic Distortion (THDi) | ≤3% (100% load) | |||
Bypass Input | Nominal Voltage(Vac) | 380/400/415 | ||
Voltage Range(Vac) | 220 Vac:25%(+10%,+15%,+20%) | |||
230 Vac:20%(+10%,+15%) | ||||
240 Vac:15%(+10%);-45%(-10%,-20%,-30%) | ||||
Phase | 3-phase in / 3-phase out | |||
Power Walking In | YES | |||
Bypass Back Irrigation | YES | |||
Generator Access | YES | |||
OUTPUT | ||||
Voltage(Vac) | 380/400/415±1% | |||
Power factor | 1 | |||
Frequency(Hz) | AC Mode | ±1%/±2%/±4%/±5%/±10% | ||
Battery Mode | (50/60±0.1%)Hz | |||
Waveform | Pure Sinewave | |||
Admissible Crest Factor | 3:01 | |||
Harmonic Distortion(THDV) | ≤2% (100%Linear Load);≤3% (100%Non-linear Load) | |||
Transfer Time(ms) | 0 | |||
Efficiency(%) | 95.50% | |||
Overload Capability | 1 hour for 110%, 10 mins for 125%,1 min for 150%, 200ms for >150% | |||
BATTERY | ||||
Maximum Charging Current(A) | 18 | |||
Nominal Voltage | ±180V/±192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc | |||
(30/32/34/36/38/40/42/44/46/48/50 pcs) | ||||
ENVIRONMENT | ||||
Operating Temperature | 0℃~40℃ | |||
Storage Temperature | -25℃~55℃ | |||
Relative Humidity | 0~95% | |||
Altitude | ||||
Noise Level(dB) | ||||
PHYSICAL | ||||
Dimension (D x W x H) mm | UPS Cabinet | 600×850×1350 | 600×850×1350 600×850×1550 | 600×850×2000 |
Module | 440×620×86 | |||
Net Weight(kg) | UPS Cabinet | 140 | 155/170 | 290 |
Module | twenty one |