Leave Your Message

Modular UPS

Brand: Banatton

Place of origin: China

Type: online UPS

Model Number: BNT9300-M 20~300KVA

Phase: Three Phase

Waveform: Pure sine wave

Transfer time: 0ms

Power factor: 0.9

Capacity: 20KVA-300KVA

Protection: short-circuit, over voltages, reverse connection protection

OEM/ODM: Yes

Supply Ability: 5000 Piece/Pieces per Month

Packaging: Carton or wooden box package or as you requested

    Description


    Brand: Banatton

    Place of origin: China

    Type: online UPS

    Model Number: BNT9300-M 20~300KVA

    Phase: Three Phase

    Waveform: Pure sine wave

    Transfer time: 0ms

    Power factor: 0.9

    Capacity: 20KVA-300KVA

    Protection: short-circuit, over voltages, reverse connection protection

    OEM/ODM: Yes

    Supply Ability: 5000 Piece/Pieces per Month

    Packaging: Carton or wooden box package or as you requested


    Features


    1. Superior energy saving.

    Efficiency > 96% at 50%-75% rated load, and >

    95% at 25% rated load; Input PF > 0.99 input THDi

    2. Easy-to install:

    Top or bottom cabling, no need of input cabling cabinet.

    3. Easy-to-maintain:

    Full front access, UPS failed part can be replaced shortly.

    4. Easy-to modify:

    The number of battery cells can be configured flexibly, so the original batteries can be used when modifying the legacy system; moreover, the battery cell can be replaced in time when it fails without interrupting the normal operation of UPS.

    5. Extra large LCD that can display 12 language (Chinese, English, Russian, French, Spanish and so on).

    6. Provide large LCD touch screen(optional).

    7. Each UPS module provide 4 5KW charge capacity. equivalent to 10 to 12A.

    8. Advanced DSP full digital control technologies realize higher system stability, online capacity expansion and maintenance.

    9. Advanced distributed active parallel technology realizes parallel operation of 4 UPS units and online capacity expansion without centralized bypass cabinet.

    10. Adaptive to severe power grid environment due to extra wide input voltage and frequency ranges.

    11. Intelligent battery management maintains battery automatically to prolong the battery life.

    12. The machine system for modular structure, consists of 1 to 10 module's biggest single module to 30kw.

    13. UPS power module supporting hot swappable, capacity upgrade extremely simple.

    14. Super ability forover load and short circuit, ensure the system stability and safety under the limit state of system.


    Modular UPS (7).jpg


    Modular UPS (8).jpg


    Modular UPS (9).jpg


    Little Hint


    1. In the warranty period the machine has a problem, please contact the sales staff, we will be responsible for customer service.

    2. Exceed the warranty period, improper operation and man-made damage, we will still give help and support, we will provide spare parts at a cost price.

    3. According to the customer's needs, we can provide unconventional, but the cost may be slightly higher than the traditional machine.


    Applications


    Modular UPS (10).jpg


    Data processing center, The host system, Computer servers, Medical, Traffic, Electricity, IT, Industrial and other industries.


    Factory Production Line


    Modular UPS (11).jpg


    Modular UPS (12).jpg


    Modular UPS (13).jpg


    Packaging


    Modular UPS (14).jpg

    MODEL

    BNT990-M

    BNT9150/180-M

    BNT9300-M

    Rated Capacity

    Cabinet Capacity

    20-90kVA / 20-90kW

    25-150kVA / 25-150kW  30-180kVA / 30-180kW

    30-300kVA / 30-300kW

    One Ppwer Module Capacity

    20kVA /20kW, 25kVA /25kW,30kVA /30kW

    MAX. Power Module NO.

    3

    5/6

    10

    INPUT


    Main Input

    Nominal Voltage(Vac)

    380/400/415

    Voltage Range(Vac)

    138~485Vac;305~485Vac load,138~305Vac load

    Phase

    3-phase in / 3-phase out

    Nominal Frequency(Hz)

    40-70

    Power Factor

    ≥0.99

    Harmonic Distortion (THDi)

    ≤3% (100% load)

    Bypass Input

    Nominal Voltage(Vac)

    380/400/415

    Voltage Range(Vac)

    220 Vac:25%(+10%,+15%,+20%)

    230 Vac:20%(+10%,+15%)

    240 Vac:15%(+10%);-45%(-10%,-20%,-30%)

    Phase

    3-phase in / 3-phase out

    Power Walking In

    YES

    Bypass Back Irrigation

    YES

    Generator Access

    YES

    OUTPUT


    Voltage(Vac)

    380/400/415±1%

    Power factor

    1

    Frequency(Hz)

    AC Mode

    ±1%/±2%/±4%/±5%/±10%

    Battery Mode

    (50/60±0.1%)Hz

    Waveform

    Pure Sinewave

    Admissible Crest Factor

    3:01

    Harmonic Distortion(THDV)

    ≤2% (100%Linear Load);≤3% (100%Non-linear Load)

    Transfer Time(ms)

    0

    Efficiency(%)

    95.50%

    Overload Capability

    1 hour for 110%, 10 mins for 125%,1 min for 150%, 200ms for >150%

    BATTERY


    Maximum Charging Current(A)

    18

    Nominal Voltage

    ±180V/±192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc

    (30/32/34/36/38/40/42/44/46/48/50 pcs)

    ENVIRONMENT


    Operating Temperature

    0℃~40℃

    Storage Temperature

    -25℃~55℃

    Relative Humidity

    0~95%

    Altitude

    Noise Level(dB)

    PHYSICAL


    Dimension (D x W x H) mm

    UPS Cabinet

    600×850×1350

    600×850×1350 600×850×1550

    600×850×2000

    Module

    440×620×86

    Net Weight(kg)

    UPS Cabinet

    140

    155/170

    290

    Module

    twenty one